IEC/EN 60079-7
GOST R IEC 60079-7
IEC/EN 60079-10
GOST IEC 60079-10
IEC/EN 60079-14
GOST IEC 60079-14
Ex marking for type of protection Ex ec IIC T3 Gc
II
3
G
Ex
ec
IIC
T3
Gc
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
AA87
2
Ex
nA
IIC
T3
Gc
X
①
⑪
②
⑫
⑥
⑦
⑧
⑨
⑩
⑬
①
CE- or EAC marking
②
Code for prevention of explosions
③
Equipment group: II not for mining, but other hazardous zones
④
Device category: 3 for infrequent, short-term danger
⑤
Atmosphere: G for gas
⑥
Explosion protection: International
⑦
Type of protection: "ec"
⑧
Explosion group: IIC for acetylene
⑨
Temperature Class: T3 for maximum surface temperature 200 °C
⑩
Device protection level: Gc for an extended level of protection in hazardous zones with
explosive gas mixtures
⑪
Identification number or name of nominated testing agency
⑫
Zone 2
⑬
"X" special conditions
Ex marking for type of protection Ex ec IIB T3 Gc
II
3
G
Ex
ec
IIB
T3
Gc
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
AA87
2
Ex
nA
IIB
T3
Gc
X
①
⑪
②
⑫
⑥
⑦
⑧
⑨
⑩
⑬
Description
SIMOTICS FD 1MM1
Operating Instructions 02/2019
23
Summary of Contents for SIMOTICS FD 1MM1 Series
Page 2: ...05 02 2019 16 03 V11 01 ...
Page 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Page 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Page 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Page 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Page 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Page 177: ......