Description
3
Applications
This electrical machine has been designed for a wide range of drive and energy conversion
applications. The machines are characterized by extreme ruggedness, long service life, and
overall reliability. They are also highly versatile, allowing them to be tailored to specific
functions.
Details of the supplied machine and permissible operating conditions can be found in this
documentation.
The machine was designed in accordance with the ordering party's specification and may only
be used for the contractually agreed purpose. The permissible operating conditions are
specified on the rating plate. The technical data are described in the catalog.
Type of protection Ex ec
This machine has type of protection Ex ec according to IEC / EN 60079-7. It can therefore be
operated in hazardous areas of Zone 2 according to IEC / EN 60079‑10-1.
WARNING
Explosion hazard
This machine is not designed for use in areas at risk of dust explosion or in areas where an
explosion hazard exists due to hybrid mixtures. An explosion can occur if the machine is
operated in these areas. This can result in death, serious injury or material damage.
● Never operate this machine in the presence of explosive dust or in areas where an
explosion hazard exists due to hybrid mixtures.
Machine design
The regulations and standards used as the basis to design and test this machine are stamped
on the rating plate.
The machine design basically complies with the subsequent standards. Please refer to the EU
Declaration of Conformity for the versions of the harmonized standards referenced.
Table 3-1
Machine design
Feature
Standard
Rating and performance
IEC/EN 60034‑1
Degree of protection
IEC/EN 60034‑5
Cooling
IEC/EN 60034‑6
Type of construction
IEC/EN 60034‑7
SIMOTICS FD 1MM1
Operating Instructions 02/2019
21
Summary of Contents for SIMOTICS FD 1MM1 Series
Page 2: ...05 02 2019 16 03 V11 01 ...
Page 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Page 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Page 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Page 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Page 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Page 177: ......