● Charge transfer limit
– 60 nC for Group I or Group IIA devices
– 25 nC for Group IIB devices
– 10 nC for Group IIC devices
– 200 nC for Group III devices (values not valid for strongly charge generating processes)
● Breakdown voltage ≤ 4 kV for explosion group III (gas and dust)
Suitability test of the paint system for hazardous areas
Proof is available for the electrostatic suitability with explosion-proof machines for the paint
systems ordered by default. Such evidence is not available for paint systems that are non-
standard or specifically requested by customers. Take into consideration that the provided
evidence is not valid for repaintings.
9.1.14
Maintaining terminal boxes
Requirement
The machine is de-energized.
Checking the terminal box
● Terminal boxes must be regularly checked for tightness, undamaged insulation, and tight
terminal connections.
● If dust or humidity have infiltrated the terminal box, this should be cleaned and dried
(particularly the insulators).
Check all the seals and sealing surfaces and address the cause of the leakiness.
● Check the insulators, connectors and cable connections in the terminal box.
● Replace any damaged components.
WARNING
Short-circuit hazard
Short-circuits can occur as a result of damaged components. This can result in death,
serious injury or material damage.
Replace damaged components.
Maintenance
9.1 Inspection and maintenance
SIMOTICS FD 1MM1
Operating Instructions 02/2019
129
Summary of Contents for SIMOTICS FD 1MM1 Series
Page 2: ...05 02 2019 16 03 V11 01 ...
Page 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Page 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Page 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Page 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Page 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Page 177: ......