Functions
5.1 Basic functions
3KC ATC6500 transfer control device
62
Manual, 05/2019, L1V30538268002A-01
5.1.6.1
Features of the alarms
Various features can be assigned to each alarm, including the user alarms (UAx see chapter
User alarms (Page 67)).
●
Alarms enabled (Enable)
General enabling of the alarm. If an alarm has not been enabled, the procedure is as if
the alarm did not exist.
●
AUT only (Aut)
The alarm can only be triggered if the ATC6500 is in automatic mode.
●
Retention alarm (Retent)
Remains stored, even after the triggering cause has been removed.
●
Global alarm A (Glb-A)
Activates the output which is assigned to this function.
●
Global alarm B (Glb-B)
Activates the output which is assigned to this function.
●
Lock breaker 1 (Lock 1)
On occurrence of the alarm, no further commands are sent to Breaker 1.
●
Lock breaker 2 (Lock 2)
On occurrence of the alarm, no further commands are sent to breaker 2.
●
Siren (Siren)
Activates the output assigned to this function, as configured in the table of alarms
●
Inhibition (inhibit)
The alarm can be temporarily deactivated by activating a programmable input with the
alarm inhibit function.
●
Modem
The alarm is sent via the modem (SMS or FTP)
●
No LCD (No LCD)
The alarm is managed normally, but not shown on the display.