Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
165
9.4.3
P03 - Password
The parameters for enabling / disabling the password are described below.
For entering the password, please refer to chapter Password protection (Page 52)
Note
Note the password
Please make a note of the new password that has been entered. Loss of this password
means that the device can no longer be parameterized. Please contact Siemens Technical
Support in this case.
P03
Designation on ATC
display
Description
Unit
Default Range
P03.01
ENABLE PASSWORD Enable password protection
– If this parameter is set to OFF, no password protec-
tion is enabled. This means that all parameters can
be changed on access to the ATC.
ON
OFF/ON
P03.02
USER PASSWORD
Password user level
Under this parameter and in connection with param-
eter P03.01 a numeric code is set for the user level
password. (See chapter Password protection
(Page 52))
1000
0-9999
P03.03
ADVANCED
PASSWORD
Password advanced level
– Under this parameter and in connection with pa-
rameter P03.01 a numerical code is set for the ad-
vanced level password. (See chapter Password
protection (Page 52))
2000
0-9999
P03.04
REMOTE
PASSWORD
Password remote access
– Under this parameter a numerical code is set for
the password for remote access via MODBUS. This
is independent from the parameter P03.01.
3000
OFF/ 1-
9999