Connection
7.4 Connection of 3VA molded case circuit breakers
3KC ATC6500 transfer control device
114
Manual, 05/2019, L1V30538268002A-01
Note
Mechanical / electrical interlocks
The two breakers of the infeed sources are not interlocked in the circuit diagram shown
above. A mechanical interlock cannot be applied either (see chapter Transfer between 2
sources, with 3 switching devices (Page 95))
Note
Expansion modules
For additional functions, expansion modules with inputs/outputs can be attached if necessary
(see chapter Expansion modules (Page 209)).
You can find more information on the technical specifications of the circuit breaker in the
Manual "3VA Molded Case Circuit Breakers"
https://support.industry.siemens.com/cs/ww/en/view/90318775
Terminal
Parameter code
Settings
-
P02.01 System configuration
2S-1T-SI or 2S–1T-AI
-
P02.22 Management of the tie breaker (TB) Breaker pulse or breaker continuous
-
P08.01 Type of breaker
Breaker pulse or breaker continuous
40 (INP1)
P12.1.01 Function of the input INP1
Source 1 breaker closed (feedback 1)
41 (INP2)
P12.2.01 Function of the input INP2
Source 2 breaker closed (feedback 2)
42 (INP3)
P12.3.01 Function of the input INP3
Tie breaker TB / NPL closed (feedback message)
43 (INP4)
P12.4.01 Function of the input INP4
Source 1 breaker protection (Trip 1)
44 (INP5)
P12.05.01 Function of the input INP5
Source 2 breaker protection (Trip 2)
45 (INP6)
P12.06.01 Function of the input INP6
Tie breaker protection (Trip)
55 (OUT1) P13.1.01 Function of the output OUT1
Open Source 1 breaker
57 (OUT2) P13.2.01 Function of the output OUT2
Close Source 1 breaker
58 (OUT3) P13.3.01 Function of the output OUT3
Open Source 2 breaker
60 (OUT4) P13.4.01 Function of the output OUT4
Close Source 2 breaker
14 (OUT12) P13.12.01 Function of the output OUT12
Open tie breaker TB / NPL
24 (OUT13) P13.13.01 Function of the output OUT13
Close tie breaker TB / NPL