Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
181
9.4.15
P15 - User limit thresholds LIMx
You can find more information on the limit thresholds in chapter Limit threshold LIMx
(Page 75).
P15
n=1…16
Designation
on ATC dis-
play
Description
Unit
De-
fault
Range
P15.n.01 REFERENCE
MEASURE
Reference measurement -
- Defines which measurements of the ATC6500 the limit
threshold is applied to. For the list of reference measure-
ments, refer to chapter Limit threshold LIMx. (Page 75)
OFF See chapter
P15.n.02 REFERENCE
SOURCE
Source reference measurement
– If the reference measurement involves an electrical
measurement, this parameter specifies whether it refers to
Source 1 or Source 2.
OFF OFF
SRC1
SRC2
P15.n.03 CHANNEL
NO.
No. channel no. (x)
– If the reference measurement is an internal multi-channel
measurement, the channel number is defined here.
1
OFF / 1-99
P15.n.04 FUNCTION
Function
– Defines the mode of operation of the limit threshold (see
chapter User limit threshold LIMx (Page 75))
MAX MAX
MIN
MIN+MAX
P15.n.05 UPPER
THRESHOLD
Upper threshold
– Defines the upper threshold obtained by multiplying the
value of P15.n.05 by the value of P15.n.06.
0
-9999 - + 9999
P15.n.06 MULTIPLIER Multiplier
- See parameter 15.05
x1 -100 -x10k
P15.n.07 DELAY
Delay
– Upper threshold intervention delay.
sec
0
0.0-600.0
P15.n.08 LOWER
THRESHOLD
Lower threshold
– Defines the lower threshold obtained by multiplying the
value of P15.n.08 by the value of P15.n.09.
0
-9999 - + 9999
P15.n.09 MULTIPLIER Multiplier
- See parameter 15.08
x1 -100 - x10k
P15.n.10 DELAY
Delay
- See parameter 15.08
sec
0
0.0 – 600.0
P15.n.11 NORMAL
STATUS
Normal status
– Used for reversing the status of the threshold LIMn.
OFF OFF-ON
P15.n.12 MEMORY
Memory
– Defines whether the threshold remains stored and must
be reset manually via the Commands menu (ON) or is
automatically reset (OFF).
OFF OFF-ON