Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
176
Manual, 05/2019, L1V30538268002A-01
P09
Qn,
n=1…2
Designation on
ATC display
Description
Unit De-
fault
Range
P09.n.19 INTERNAL SRC
CONTROL
Enable control of the source
- With this parameter it is possible to set whether the source is
only regarded as OK subject to a condition.
OFF = The source can be connected normally.
Every other setting = The source can only be used if the variable
is active.
OFF OFF
INPx
OUTx
LIMx
REMx
Ax
Uax
TIMx
P09.n.20 CHANNEL NO. Function index (x)
- Index that is possibly assigned to the function programmed in
the previous parameter.
Example:
Source 1 should only be controllable if the input 4 has been ena-
bled:
P08.1.19 = INPx
P08.1.20 = 4
OFF OFF / 1-
99
1)
OFF = The voltage measurement in the OFF mode is disabled.
2)
ON = The voltage measurement in the OFF mode is enabled.
3)
OFF+GLOB = The voltage measurement in the OFF mode is disabled but the relay programmed for the global alarm
function is either tripped or not, depending on whether the source is present or missing.
4)
ON+GLOB = The voltage measurement in the OFF mode is enabled and the relay programmed for the global alarm
function is either tripped or not, depending on whether the source is present or missing.