Connection
7.2 General connection drawings
3KC ATC6500 transfer control device
100
Manual, 05/2019, L1V30538268002A-01
Terminal
Parameter code
Settings
-
P02.01 System configuration
2S – 1T – SI or 2S – 1T - AI
-
P02.22 Management of the tie breaker (TB)
Breaker pulse or breaker continuous
-
P08.01 Type of breaker
Breaker pulse or breaker continuous
40 (INP1)
P12.1.01 Function of the input INP1
Source 1 breaker closed (feedback 1)
41 (INP2)
P12.2.01 Function of the input INP2
Source 2 breaker closed (feedback 2)
42 (INP3)
P12.3.01 Function of the input INP3
Tie breaker TB / NPL closed (feedback message)
43 (INP4)
P12.4.01 Function of the input INP4
Source 1 breaker protection (Trip 1)
44 (INP5)
P12.05.01 Function of the input INP5
Source 2 breaker protection (Trip 2)
45 (INP6)
P12.06.01 Function of the input INP6
Tie breaker protection (Trip)
55 (OUT1) P13.1.01 Function of the output OUT1
Open Source 1 breaker
57 (OUT2) P13.2.01 Function of the output OUT2
Close Source 1 breaker
58 (OUT3) P13.3.01 Function of the output OUT3
Open Source 2 breaker
60 (OUT4) P13.4.01 Function of the output OUT4
Close Source 2 breaker
20 (OUT7) P13.7.01 Function of the output OUT7
Open tie breaker TB / NPL
31 (OUT9) P13.9.01 Function of the output OUT9
Close tie breaker TB / NPL