Connection
7.5 Connection of the 3WL air circuit breaker
3KC ATC6500 transfer control device
122
Manual, 05/2019, L1V30538268002A-01
Note
Implementation of the power supply
More information on implementing the power supply of the ATC6500 via the inputs 53, 54
and / or the inputs 26, 27 can be found in chapter Connection of the power supply (Page 83).
Note
Mechanical interlock
A mechanical interlock of the circuit breakers can be applied in addition.
Note
Expansion modules
For additional functions, expansion modules with inputs/outputs can be attached if necessary
(see chapter Expansion modules (Page 209)).
You can find more information on the technical specifications of the circuit breaker in the
Manual "3WL10 air circuit breakers and 3VA27 molded case circuit breakers"
https://support.industry.siemens.com/cs/ww/en/view/109753821
Terminal
Parameter code
Settings
-
P02.01 System configuration
A: 2S-0T
-
P02.22 Management of the tie breaker
(TB)
OFF
-
P08.01 Type of breaker
Breaker pulse or breaker continuous
40 (INP1)
P12.1.01 Function of the input INP1
Source 1 breaker closed (feedback 1)
41 (INP2)
P12.2.01 Function of the input INP2
Source 2 breaker closed (feedback 2)
42 (INP3)
P12.3.01 Function of the input INP3
Source 1 breaker protection (Trip 1)
43 (INP4)
P12.4.01 Function of the input INP4
Source 2 breaker protection (Trip 2)
55 (OUT1) P13.1.01 Function of the output OUT1
Open Source 1 breaker
57 (OUT2) P13.2.01 Function of the output OUT2
Close Source 1 breaker
58 (OUT3) P13.3.01 Function of the output OUT3
Open Source 2 breaker
60 (OUT4) P13.4.01 Function of the output OUT4
Close Source 2 breaker