Technical specifications
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
239
Relay outputs OUT7, OUT9, OUT10: Terminals 19-21, 30-32, 33-35
Contact type
3 x 1 CO contact
Rated contact current
AC1 8A 250V
AC15 1.5A 250V
DC1 8A 30V
UL Rating
B300
30 VDC 1 A auxiliary duty
Output voltage (maximum)
250 VAC
Mechanical/electrical endurance (cycle)
1x10^7 / 1x10^5
Insulation voltage U
i
250 VAC
Impulse withstand voltage U
imp
OUT7, OUT9, OUT10 7.3 kV
Power frequency withstand voltage OUT7, OUT9,
OUT10
3 kV
Ambient conditions
Operating temperature
-30 …+70 °C
Storage temperature
-30 …+80 °C
Relative humidity
<80 % (IEC / EN 60068-2-78)
Maximum degree of pollution
2
Overvoltage category
3
Measuring category
CAT III
Connections
Connecting terminals
Removable / plug-in
Cable cross-section (min-max)
0.2 …2.5 mm2 (AWG 24 ... 12)
Cable cross-section (min-max) acc. to UL 508
0.75 …2.5 mm2 (AWG 18 ... 12)
Tightening torque
0.56 Nm (5 lbf in)
Enclosure
Enclosure material
Polycarbonate
Version
Door installation
Degree of protection
IP40 at front (can be increased to IP65 by using IP protective seal),
IP20 at rear
Weight
680 g
Certifications and approvals
The following standards are complied with:
EAC, cULus
Complies with standards
IEC / EN 61010-1, IEC / EN 61010-2,
IEC / EN 61000-6-3, IEC / EN 61000-6-4,
UL508, CSA C22.2-N°14
UL marking
Use 60°C/75°C copper (CU) conductor only
AWG Range: 18 - 12 AWG stranded or solid
Field Wiring Terminals Tightening Torque:
4.5lb.in
Flat panel mounting on a Type 1 or 4X enclosure
Note: This product is designed for environment A. Its use in a Class B environment can lead to unwanted electromagnetic
problems. Consideration should be given to possible measures for mitigating the electromagnetic radiation.