Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
166
Manual, 05/2019, L1V30538268002A-01
9.4.4
P04 - Battery
Note
Use of DC power supply
The following parameters are necessary only if you are using a DC power supply (see
chapter Connecting the power supply (Page 83)).
P04
Designation on
ATC display
Description
Unit
Default
Range
P04.01 BATTERY
VOLTAGE
Nominal voltage of the battery
– This parameter defines the voltage of the additional DC
supply of the ATC6500.
Note: If this parameter is set to OFF, all alarms regarding
the DC supply, as well as the indicator for the battery volt-
age, are disabled.
V
AUTO
AUTO
12
24
48
OFF
P04.02 MAX. VOLTAGE
LIMIT
Maximum limit for battery voltage
– This defines the upper limit threshold for the battery volt-
age
%
130
110-
140
P04.03 MIN. VOLTAGE
LIMIT
Minimum limit for battery voltage
– This defines the lower limit threshold for the battery volt-
age
%
75
60-130
P04.04 MIN/MAX
VOLT.DELAY
Delay for minimum / maximum battery voltage
– This parameter defines the delay for the mini-
mum / maximum battery voltage. If the voltage exceeds the
upper or lower limits from P04.02 and P04.03 for the peri-
od defined by this parameter, the corresponding alarms
are triggered.
s
10
0-120