3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
237
Technical specifications
13
Auxiliary power supply: Terminal 53,54
Supply voltage U
s
100 - 240 VAC
110 - 250 VDC
Operating range
90 - 264 VAC
93.5 - 300 VDC
Operating frequency
45 - 66 Hz
Power loss (max.)
at 100 VAC: 5.3W
at 240 V AC: 5.5W
Power consumption (max.)
12.5 VA
Interference strength against voltage dips
at 240 VAC:
- without expansion modules
≤
40 ms (at 110 VAC)
≤
200 ms (at 220 VAC)
- with 3 expansion modules
≤
20 ms (at 110 VAC)
≤
100 ms (at 220 VAC)
Recommended fuse
F1A (quick-response)
Insulation voltage U
i
250 VAC
Impulse withstand voltage U
imp
7.3 kV
Power frequency withstand voltage
3 kV
DC power supply: Terminal 26,27
Battery power supply
12 - 48 VDC
Operating range of battery power supply
7.5 - 57.6 VDC
Current consumption (max.)
400 mA at 12 VDC
220 mA at 24 VDC
100 mA at 48 VDC
Power loss (max.)
4.8 W
Recommended fuse
T3,15A (slow)
Voltage measuring inputs: Terminals 1-4 and 5-8
Nominal voltage U
e
(maximum)
600 VAC L-L (346 VAC L-N)
Measuring range
50 - 720 VAC L-L (30…415 VAC L-N)
Frequency range
45-65 Hz
Measuring method
True RMS
Impedance of measuring input
> 0.55 M
Ω
L-N
> 1.1 M
Ω
L-L
Connection method
Single-phase, two-phase, or three-phase system
Measuring accuracy
± 0.25 %,
value range ± 1 digit
Insulation voltage U
i
600 VAC
Impulse withstand voltage U
imp
9.8 kV
Power frequency withstand voltage
5.2 kV