Maintenance
9410 series
NOTICE
DATA LOSS
Failure to follow these instructions can result in data loss.
Ensure that all important data has been recorded before uploading firmware or a
template to your device.
1. Obtain the meter firmware (.UPG) and framework (.DCF) that you want to load onto
your meter. Save the files where they can be accessed by the computer running
ION Setup.
2. Start ION Setup.
3. Open the Setup Assistant for your meter.
4. Select the
Template
screen.
5. Click the
Firmware Upgrade
tab, then click
Upgrade
. Enter your meter’s password
(if prompted) and click
OK
.
6. Navigate to the meter firmware (.UPG) file and click
Open
. Enter your ION Setup
password when prompted and click
OK
.
7. Navigate to the meter framework (.DCF) file and click
OK
.
The Template Paste Options dialog box appears.
8. Select the check boxes for the settings you want to retain (not overwrite) and click
OK
.
A dialog box describes the template upload and firmware upgrade progress, verifies
the firmware, and finishes with an overview stating whether the firmware and
framework were successfully uploaded onto your meter.
Loading option module firmware using ION Setup
You can upload firmware to your meter’s option modules using ION Setup over an
Ethernet connection.
You can only upload firmware to the same type of module; if you have different types of
option modules connected to your meter, you must perform the upload process for
each module type.
You must have:
•
Your meter’s option module firmware upgrade (.SI9) file. You can download
upgrade files from www.usa.siemens.com/pds.
•
The option module connected to your meter, and have access to your meter’s
internal FTP site.
•
FTP access to your meter from the computer running ION Setup.
All option modules do not perform their regular functions during firmware upgrade; they
will not communicate to the meter and the outputs may change state during the
upgrade process.
WARNING
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Do not use this device for critical control or protection applications where human or
equipment safety relies on the operation of the control circuit.
7EN05-0336-01