9410 series
Basic setup
Basic setup
Default values for commissioning
Use these default settings for the first time you connect to and configure your meter.
Parameter
Default value
Display password (also for logging onto meter webpages)
0
Username (for logging onto meter webpages)
9410
IP address
169.254.0.10
Subnet mask
255.255.0.0
Gateway
0.0.0.0
Unit ID
1
Language
English
Meter setup
You can configure your meter’s basic metering parameters using the display.
Volts mode
Parameter
Values
Description
Volts Mode
4W-Wye, Delta, 3W-Wye,
Single, Demo
The power system’s configuration
PhaseOrder
ABC, ACB
The power system’s phase order
PT/CT setup
Parameter
Values
Description
PT Primary
1 to 999,999.99
The potential transformer’s primary winding voltage
rating
NOTE:
PTs are also referred to as a VTs or voltage
transformers.
PT Secondary
1 to 999,999.99
The potential transformer’s secondary winding
voltage rating
NOTE:
PTs are also referred to as a VTs or voltage
transformers.
CT Primary
1 to 999,999.99
The current transformer’s primary winding current
rating
CT Secondary
1 to 999,999.99
The current transformer’s secondary winding
current rating
I4 Primary
1 to 999,999.99
The I4 current transformer’s primary winding
current rating
I4 Secondary
1 to 999,999.99
The I4 current transformer’s secondary winding
current rating
16
7EN05-0336-01