9410 series
Logging
Related Topics
•
Setpoint learning overview
•
COMTRADE
•
Minimum configuration requirements for basic metering
Default waveform recording configuration
Your meter’s waveform recording operates once your nominal values are configured.
Your meter has the following default waveform recorders:
Waveform recorder
Description
Wfm Rc V1-Sg/Sw
V1 voltage waveforms recorded during a defined sag or swell event.
Wfm Rc V2-Sg/Sw
V2 voltage waveforms recorded during a defined sag or swell event.
Wfm Rc V3-Sg/Sw
V3 voltage waveforms recorded during a defined sag or swell event.
Wfm Rc I1-Sg/Sw
I1 current waveforms recorded during a defined sag or swell event.
Wfm Rc I2-Sg/Sw
I2 current waveforms recorded during a defined sag or swell event.
Wfm Rc I3-Sg/Sw
I3 current waveforms recorded during a defined sag or swell event.
Configuring waveform recording using ION Setup
You can configure waveform recording using ION Setup.
For waveform recording to trigger automatically, you must enter your system’s nominal
(normal) voltage and current values, and then the amount of deviation from the
nominal required to trigger waveform recording.
Changing your meter’s waveform recording configuration clears your meter’s existing
waveform records.
NOTICE
DATA LOSS
Failure to follow these instructions can result in equipment damage.
Ensure that all important data has been recorded before configuring waveform
recording.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Alarming
and click the
Sag/Swell
tab. Configure your meter’s sag/
swell detection parameters.
108
7EN05-0336-01