Communications
9410 series
Link (data rate)
On: valid Ethernet connection
•
Yellow: data rate is 10 Mbps
•
Green: data rate is 100 Mbps
Act (activity)
Flashing green: data is being transferred
Ethernet configuration
In order to use Ethernet communications, you must configure your device’s IP
address; you must also configure the subnet and gateway information if required by
your network.
NOTE:
For meters that do not have a display, you must configure each one separately
in order to set a unique IP address for each device.
You need to enter network information for any Ethernet servers used by the device.
NOTE:
Contact your network system administrator for your IP address and other
Ethernet network configuration values.
Configure your device’s Ethernet settings by using the display or directly connecting to
your meter and using a web browser to access the device’s webpages. Modify your
meter’s Ethernet settings to those provided by your network system administrator
before connecting the device to your local area network (LAN).
After the meter’s Ethernet port is configured and connected to the LAN, you can use
ION Setup to configure other meter setup parameters.
Protocols, ports and connections
The Ethernet protocols supported by your device allow simultaneous connections
through the IP service ports.
Protocol
Port (default)
Number of
connections
ION
7700
8
1
DNP
20000
Modbus TCP
502
Modbus RTU over Ethernet
7701
Modbus TCP (dedicated)
502
32
EtherGate
7801
1
FTP
21 (20)
2
Webserver (HTTP)
2
80
10
SNMP
161
N/A
SMTP server (email) outgoing only
25
1
NTP
123
1
IEC 61850
102
4
1
These 8 simultaneous connections can be used by ION, Modbus TCP, Modbus RTU over Ethernet, or
DNP. You can have a maximum of 3 DNP connections.
2
This is used for the meter’s webpages.
By enabling or disabling TCP/IP protocols, you can control whether or not your meter
accepts new socket connection requests from the TCP/IP protocols supported by the
meter. Changing settings does not impact existing connections. Depending on the
protocol, you can also change the port number.