9410 series
Inputs / outputs
for your energy system. For applications requiring high accuracy, such as energy
pulsing to verify accuracy, the digital output on the meter base is recommended.
Your meter’s digital and analog outputs may change state during a firmware upgrade.
Option modules are offline during an option module firmware upgrade; they will not
communicate to the meter and the outputs may change state during the upgrade
process.
Your meter’s analog I/O option modules can measure and output either low voltage or
current using standard analog transducers such as 4 - 20 mA current transducers.
Analog I/O option module data viewing
View analog I/O option module data from the webpages and display.
To view analog option module data on your meter’s display, go to
Inputs/Outputs
and
select either
Analog Inputs
or
Analog Outputs
. If there are no I/O of the specified
type, an informative message is displayed.
To view analog option module data on your meter’s webpages, connect to your meter’s
webpages, go to
Monitoring > Inputs/Outputs
and select either
Analog Inputs
or
Analog Outputs
. If there are no I/O of the specified type, an informative message is
displayed.
Digital I/O option module data viewing
View digital I/O option module data from the webpages and display.
To view digital option module data on your meter’s display, go to
Inputs/Outputs
and
select either
Digital Inputs
or
Digital Outputs
. If there are no I/O of the specified type,
an informative message is displayed.
To view digital option module data on your meter’s webpages, connect to your meter’s
webpages, go to
Monitoring > Inputs/Outputs
and select either
Digital Inputs
or
Digital Outputs
. If there are no I/O of the specified type, an informative message is
displayed.
Analog inputs
Analog input applications
You can use an analog input to monitor an analog flowmeter to monitor how much
water flows through a pipe.
For analog input operation, your meter takes an analog input signal and provides the
resulting scaled value.
Your meter’s analog I/O option modules can measure either low voltage or current
using standard analog transducers such as 4 - 20 mA current transducers.
Related Topics
•
Specifications
Analog input voltage and current mode
You can set the analog input’s mode for voltage or current sensing.
In current mode, the analog inputs have a low input resistance while the meter is
powered on, and a high input resistance when the meter is powered off. In voltage
mode, the analog inputs have a high input resistance regardless of whether the meter
is powered or not.
114