Alarms and alerts
9410 series
priority is greater than the event log cutoff value, the associated event is recorded in
the meter’s event log. If the alarm’s priority is set to
None
, the event priority is
automatically set to zero, and no associated event is logged in the meter’s event log.
For events that you want to log for future reference or troubleshooting, but don’t want
alarm functions, set the alarm priority to
Info Only
.
For nuisance events that frequently occur and you have no desire to log for reference
or troubleshooting, set the alarm priority to
None
.
Related Topics
•
Event log overview
Alarm indicators
Your meter’s display has an alarm indicator to show you what alarm levels have been
detected (active or historic) and whether they have been acknowledged.
For active high priority alarms, the meter’s display will also flash until the alarm is
acknowledged. There is also an alarm LED to indicate the meter’s alarm condition.
Alarm
Alarm icon
Alarm icon flash
Alarm LED
Meter display
Active high
Red solid bell
Flash if not acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
Flash if not acknowledged
Active medium
Yellow solid bell
Flash if not acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Active low
Blue solid bell
Flash if not acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic high
Red outline bell
Flash if not acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic medium
Yellow outline bell
Flash if not acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic low
Blue outline bell
Flash if not acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
No active or
unacknowledged alarms
Gray solid bell
No flash
Off
No flash
If there are multiple active alarms, the meter displays the alarm condition associated
with the most important active alarm. If there are multiple unacknowledged historic
alarms, the meter displays the alarm condition associated with the most important
unacknowledged historic alarm.
NOTE:
To stop an alarm from being displayed without impacting other metering
features, set the alarm priority to
Info Only
.
7EN05-0336-01
129