Hardware reference
9410 series
B
Status
C
Energy pulsing
D
Infrared energy pulsing
E
Revenue lock status
F
Remote display connection link
G
Remote display connection activity
Energy pulsing LED behavior
The visible and infrared LEDs are configured by default to pulse based on energy
measured by the meter.
You can configure the pulse weight (pulses per kWh) and the energy source.
Energy pulsing is used to help verify the energy measurement accuracy of your meter
for revenue purposes.
Related Topics
•
Energy pulsing
Revenue lock LED behavior
The revenue lock LED indicates the lock status of the meter.
State
Description
Off
The meter is not revenue locked.
On
The meter is revenue locked.
Flashing
New revenue lock state is pending; power cycle your meter to set the revenue lock
to on or off.
Remote display connection LED behavior
There are two LEDs in the remote display connector that indicate the state of
communications between the meter and remote display.
LED
Description
Green (link)
On: link established.
Off: no link established with the remote display. Check the connections to the
remote display and DIN meter.
Yellow (activity)
Flashing: active communications between the meter and the remote display.
Off: no communication activity. Check remote display and meter operation.
Panel-mount meter and remote display mounting and wiring
recommendations
There are supplemental mounting and wiring recommendations that apply to panel-
mount meters and remote displays.
•
The meter is intended to be mounted inside a ¼-DIN panel cutout.
7EN05-0336-01
21