Specifications
9410 series
Measurement accuracy
Apparent power
± 0.5%
IEC 61557-12 Class 0.5
Current (per phase)
± 0.2%
IEC 61557-12 Class 0.2
Voltage (L-N)
± 0.2%
IEC 61557-12 Class 0.2
Frequency
± 0.02%
IEC 61557-12 Class 0.02
Power quality
IEC 61000-4-30
Class S
IEC 62586
Voltage unbalance
± 0.5%
IEC 61557-12 Class 0.5
Voltage harmonics
± 2%
IEC 61557-12 Class 2
Voltage THD
± 2%
IEC 61557-12 Class 2
Current harmonics
± 2%
IEC 61557-12 Class 2
Current THD
± 2%
IEC 61557-12 Class 2
Voltage inputs
Maximum VT/PT primary
1.0 MV AC
Specified accuracy range
57 to 400 V L-N / 100 to 690 V L-L (Wye) or 100 to 600 V L-L (Delta)
Specified accuracy frequency
42 to 69 Hz (50/60 Hz nominal)
Current inputs
Specified accuracy current range
50 mA – 10 A
AC control power
Operating range
50/60 Hz ± 10%: 90 to 415 V AC L-N ± 10%
400 Hz: 90 to 120 V AC ± 10%
Ride-through time
100 ms (6 cycles at 60 Hz) min., any condition
200 ms (12 cycles at 60 Hz) typ., 120 V AC
500 ms (30 cycles at 60 Hz) typ., 415 V AC
DC control power
Operating range
120 to 300 V DC ± 10%
Ride-through time
100 ms (6 cycles at 60 Hz) min., any condition
Digital outputs
Number
1
Type
Form A solid-state
7EN05-0336-01