9410 series
Specifications
Digital outputs
Maximum load voltage
30 V AC / 60 V DC
Maximum load current
75 mA
ON resistance
13 – 40 Ω at 25 °C (77 °F)
Signal type
Continuous or pulse
Pulse frequency
≤ 25 Hz
Digital inputs
Number
3
Type
Externally excited
Event timestamp accuracy
± 1 ms
Maximum voltage
30 V AC / 60 V DC
Pulse frequency
≤ 25 Hz
IRIG-B
IRIG-B00x format (unmodulated IRIG-B time code)
Coded expressions 0 to 7 are supported but the year data is not used.
Response time
20 ms
Minimum pulse width
20 ms
Current draw
ON: ≤ 2.5 mA
OFF: ≤ 0.5 mA
Environmental characteristics
Operating temperature
-25 ºC to Max temp (-13 ºF to Max temp)
Maximum operation temperature is based on the quantity and type of attached option modules. See
Maximum operating temperature, page 166
.
Storage temperature
-40 to 85 °C (-40 to 185 °F)
Humidity rating
5 – 95% RH non-condensing
Maximum dewpoint: 37 °C (99 °F)
Pollution degree
2
Altitude
< 3000 m (9843 ft)
Location/mounting
Not suitable for wet locations
For indoor use only
Must be permanently connected and fixed
Maximum operating temperature
Max temp
948M2DO6DI
Digital (2 out, 6 in)
948M2AO4AI
Analog (2 out, 4 in)
70 ºC (158 ºF)
0 – 4
0,1
70 ºC (158 ºF)
0
2
60 ºC (140 ºF)
1, 2
2 – 4
166
7EN05-0336-01