9410 series
Alarms and alerts
Parameter
1
Description
Over I unbal
Over unbalanced current alarm
Over THD V1
V1 over total harmonic distortion (THD) voltage alarm
Over THD V2
V2 over total harmonic distortion (THD) voltage alarm
Over THD V3
V3 over total harmonic distortion (THD) voltage alarm
Over P sd
Over kW sliding demand alarm
Over Ia
Ia over current alarm
Over Ib
Ib over current alarm
Over Ic
Ic over current alarm
Over I4
I4 over current alarm
Over V unbal
Over unbalanced voltage alarm
V1 Setpoint
V1 setpoint alarm
V2 Setpoint
V2 setpoint alarm
V3 Setpoint
V3 setpoint alarm
Freq Setpoint
Frequency setpoint alarm
Sag/Swell 1
Voltage sag/swell alarm
Current Sag Ph1
Current sag alarms for phase 1
Current Sag Ph2
Current sag alarms for phase 2
Current Sag Ph3
Current sag alarms for phase 3
4-30 Volt Intrp Ph1
4-30 voltage interruption power quality alarm for phase 1
4-30 Volt Intrp Ph2
4-30 voltage interruption power quality alarm for phase 2
4-30 Volt Intrp Ph3
4-30 voltage interruption power quality alarm for phase 3
Current Swell Ph1
Current swell alarms for phase 1
Current Swell Ph2
Current swell alarms for phase 2
Current Swell Ph3
Current swell alarms for phase 3
1
Any Setpoint or Relative Setpoint module with an event priority greater than the Low alarm event priority
is also displayed on this screen.
You can only enable or disable alarms using the display. Alarm configuration is done
using ION Setup. Alarms with a priority less than
Low
(
Info Only
or
None
) are not
displayed.
You must configure all the parameters related to the alarm for alarm functions to
operate. For example, for the Over Ia alarm to operate, you must enter the nominal
value and the conditions that define an alarm state, even if the alarm is shown as
Enabled on the Alarm Setup screen.
Configuring setpoint/standard alarms using ION Setup
You can use ION Setup to configure the standard alarm settings.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Alarming
and click the
Standard
tab.
4. Select a setpoint and click
Edit
.
132