Description
3.3 Theory of Operation
FUP1010 IP67 Portable
20
Operating Instructions, 03/2012, A5E02951522-02
Flow Calibration Factor
Normally, the flow stream is in line with the axis of the pipe. On this basis, the calibration
factor of a clamp-on ultrasonic flow meter is proportional to the cosine of the beam angle
relative to the pipe axis. However, this reveals that if the angle of flow stream is not in line
with the pipe axis, the flow calibration factor could be compromised. This most often occurs
when the sensor mounting location is within close proximity of a bend or other pipe
obstruction. It is recommended that, whenever possible, mount sensors on the longest
available straight run of pipe and also use Reflect Mode mounting (as shown below).
①
Upstream Sensor
②
Downstream Sensor
③
Flow Direction
④
WideBeam transmissions exchanged between the Upstream and Downstream sensors
Reflect mounting automatically corrects for non-axial flow or cross flow conditions. When the
exchange of sonic signals occurs by reflection off the far pipe wall as shown above, the
average beam versus stream angle will be equivalent to that of an axial flow stream.
Summary of Contents for 7ME3510
Page 2: ......
Page 10: ...Table of contents FUP1010 IP67 Portable 8 Operating Instructions 03 2012 A5E02951522 02 ...
Page 159: ...1010WP 7 21614 C ...
Page 160: ...1010WP 7 21614 C ...
Page 161: ...1010WDP 7 21614 C ...
Page 162: ...1010WDP 7 21614 C ...
Page 163: ......
Page 164: ......
Page 165: ......
Page 167: ...1012FP 8 DIRECT MODE REFLECT MODE INSTALLED ON PIPE 21614 C ...
Page 168: ......
Page 169: ...21614 C ...
Page 170: ......
Page 171: ......
Page 172: ......
Page 173: ......
Page 174: ...21614 C ...
Page 175: ...21614 C ...
Page 176: ...21614 C ...
Page 177: ...21614 C ...
Page 178: ...21614 C ...
Page 179: ...21614 C ...
Page 180: ...21614 C ...
Page 181: ......
Page 182: ......
Page 183: ...21614 C ...
Page 184: ...21614 C ...
Page 185: ...1012TP S 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TP S SERIES 21614 C MOUNTING TRACK ...
Page 186: ...REFLECT MODE DIRECT MODE 21614 C ...
Page 187: ...1015BC 1 8 21614 C ...
Page 188: ...21614 C INPUT OUTPUT TERMINALS 1015WP T10 8 ...
Page 189: ...21614 C INPUT OUTPUT TERMINALS 1015WP T26 8 ...
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 195: ...DUAL HEAD CONFIGURATION 21614 C IN LINE CONFIGURATION FLOW ...
Page 196: ......
Page 197: ......
Page 208: ...Glossary FUP1010 IP67 Portable 162 Operating Instructions 03 2012 A5E02951522 02 ...
Page 212: ...Index FUP1010 IP67 Portable 166 Operating Instructions 03 2012 A5E02951522 02 ...
Page 213: ......