144
APPX
Appendix 5 Buffer Memory
Input terminal errors
The input terminal status is stored. A value to be stored is as follows.
■
Buffer memory address
The buffer memory address of this area is as follows.
■
List of input terminal errors
FX5-SF-MU4T5
FX5-SF-8DI4
Error code 1
The code of an error occurred in a module is stored. For error codes to be stored, refer to the following section.
■
Buffer memory address
The buffer memory address of this area is as follows.
Buffer memory name
Address
1st Module Input terminal error
104
2nd Module Input terminal error
144
3rd Module Input terminal error
184
Bit
Input terminal of FX5-SF-
MU4T5
Operation
b0
Input terminals I0/I1
00: No error
01: Synchronization time/concurrence error
10: Process error
11: Cross-circuit error
b1
b2
Input terminals I2/I3
b3
b4
b5
Input terminal X0
0: Open circuit connected to X terminal not detected
1: Open circuit connected to X terminal detected
b6
Input terminal X1
b7
Input terminal X2
b8 to b15
Fixed to 0
Bit
Input terminal of FX5-SF-8DI4
Operation
b0
Input terminals I0/I1
00: No error
01: Synchronization time/concurrence error
10: Process error
11: Cross-circuit error
b1
b2
Input terminals I2/I3
b3
b4
Input terminals I4/I5
b5
b6
Input terminals I6/I7
b7
b8 to b15
Fixed to 0
Buffer memory name
Address
1st Module Error code 1
105
2nd Module Error code 1
145
3rd Module Error code 1
185
Summary of Contents for MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Page 2: ......
Page 29: ...1 OVERVIEW 27 1 MEMO ...
Page 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Page 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Page 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Page 171: ...I 169 MEMO ...
Page 175: ......