4 FUNCTIONS
4.2 Built-In Program Selection Function
43
4
■
Programs that can be set for an FX5-SF-8DI4
Eight safety inputs of an FX5-SF-8DI4 are grouped into two safety inputs: INPUT A (safety input I0 to I3) and INPUT B (safety
input I4 to I7) of the rotary switch.
A program to link the four safety inputs to logic path A or B of an FX5-SF-MU4T5 can be selected by the rotary switch.
The list of built-in programs that can be set for an FX5-SF-8DI4 is as follows.
: Supported,
: Not supported,
: Not available
(1) Cross-circuit detection
(2) Synchronous time monitoring
Prog
ram
Overview
Description
Logic path A
connection (l0/l1, l2/l3)
Logic path B
connection (l4/l5, l6/l7)
Program overview
Input
device
(1)
(2)
Input
device
(1)
(2)
0
Inactive
FX5-SF-8DI4 is inactive. The input
signals are ignored.
1
AND link
(single-
channel)
Connect four safety inputs of INPUT
A or INPUT B in single-channel, and
link them to logic path A and B of an
FX5-SF-MU4T5 using AND logic.
Unused safety inputs are required
to be connected to a plus terminal
or T terminals.
N/C
N/C
(1) Connect logic path A
with AND link
(2) Connect logic path B
with AND link
2
AND link (dual-
channel) (1)
Connect four safety inputs of INPUT
A or INPUT B in dual-channel, and
link them to logic path A and B of an
FX5-SF-MU4T5 using AND logic.
Unused safety inputs are required
to be connected to a plus terminal
or T terminals.
N/C + N/C
N/C + N/C
(1) Connect logic path A
with AND link
(2) Connect logic path B
with AND link
3
AND link (dual-
channel) (2)
N/C + N/C
N/C + N/C
4
AND link (dual-
channel) (3)
N/C + N/O
N/C + N/O
5
AND link (dual-
channel) (4)
N/C + N/O
N/C + N/O
6
AND link (dual-
channel) (5)
N/C + N/C
N/C + N/C
7
OR link (dual-
channel)
Connect four safety inputs of INPUT
A or INPUT B in dual-channel, and
link them to logic path A and B of an
FX5-SF-MU4T5 using OR logic.
N/C + N/C
N/C + N/C
(1) Connect logic path A
with OR link
(2) Connect logic path B
with OR link
I0 I1 I2 I3
(1)
(2)
I4 I5 I6 I7
(1)
(2)
I0 I1 I2 I3
I4 I5 I6 I7
(1)
(2)
I4 I5 I6 I7
I0 I1 I2 I3
Summary of Contents for MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Page 2: ......
Page 29: ...1 OVERVIEW 27 1 MEMO ...
Page 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Page 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Page 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Page 171: ...I 169 MEMO ...
Page 175: ......