4 FUNCTIONS
4.12 Two-Hand Operation/Jog Mode
81
4
4.12
Two-Hand Operation/Jog Mode
Two-hand operation can be used by connecting a two-hand control device that complies with EN 574 (Two-hand control
device - Functional aspects and design principles)
A or
C to an FX5-SF-MU4T5.
Jog mode can limit the duration time which keeps the safety outputs Q2 and Q3 ON to five seconds by using a two-hand
control device. An application which can supply works during the two-hand control device operation can be constructed easily.
Setting method
Set the FUNCTION rotary switch of an FX5-SF-MU4T5 to '4' or '5'.
The jog mode is available only when '5' is set to the FUNCTION rotary switch.
For details of the wiring method, refer to the following:
Page 55 Details of the program 4 for FX5-SF-MU4T5s
Page 57 Details of the program 5 for FX5-SF-MU4T5s
Operation
*1 The duration for which the safety outputs turn ON is limited to five seconds. The duration can be reset by releasing the two-hand control
switches.
Ex.
Output examples when safety inputs are turned ON
Rotary switch
Jog mode
Settings
4
Unavailable
A two-hand control device (two dual-channel complementary N/C / N/O contacts) which complies with
EN 574
C is connected as follows.
• Cross-circuit detecting control signals (l0 to l1 and T0, l2 to l3 and T1)
5
Disabled
A two-hand control device (two single-channel N/C contacts) which complies with EN 574
A is
connected as follows. Additionally, X1 is connected to a plus terminal.
• Cross-circuit detecting control signals (l2 and T0, l3 and T1)
Enabled
A two-hand control device (two single-channel N/C contacts) which complies with EN 574
A is
connected as follows. Additionally, X1 is disconnected from a plus terminal.
• Cross-circuit detecting control signals (l2 and T0, l3 and T1)
Rotary switch
Jog mode
Operation
4
Unavailable
Safety inputs of I0 to I3 turn ON only when two-hand control switches (
C) are pressed simultaneously
within 0.5 seconds.
5
Disabled
Safety inputs of I2 to I3 turn ON only when two-hand control switches (
A) are pressed simultaneously
within 0.5 seconds.
Enabled
Safety inputs of I2 to I3 turn ON only when two-hand control switches (
A) are pressed down
simultaneously within 0.5 seconds.
Rotary switch
Jog mode
Safety inputs
Safety outputs
I0
I1
I2
I3
Q0
Q1
Q2
Q3
4
Unavailable
ON
ON
ON
ON
5
Disabled
ON
ON
ON
Enabled
ON
ON
ON
Summary of Contents for MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Page 2: ......
Page 29: ...1 OVERVIEW 27 1 MEMO ...
Page 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Page 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Page 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Page 171: ...I 169 MEMO ...
Page 175: ......