10 TROUBLESHOOTING
10.4 List of Error Codes
125
10
3341H to
3342H
Memory error
A memory error occurred.
Check the setting and wiring, and reset the power of the whole
system.
If the error is not resolved, there is a possibility that the module is
malfunctioning.
Please contact your local Mitsubishi Electric sales office or
representative.
3401H to
3408H
Self-diagnostic error
A self-diagnostic error occurred.
Check the setting and wiring, and reset the power of the whole
system.
If the error is not resolved, there is a possibility that the module is
malfunctioning.
Please contact your local Mitsubishi Electric sales office or
representative.
341BH
Self-diagnostic error
A self-diagnostic error occurred.
Check the setting and wiring, and reset the power of the whole
system.
If the error is not resolved, there is a possibility that the module is
malfunctioning.
Please contact your local Mitsubishi Electric sales office or
representative.
3501H to
35FFH
An error occurred in the internal circuit of an input terminal lx
corresponding to the bits which are ON.
35
H
• b0: I0
• b1: I1
• b2: I2
• b3: I3
• b4: I4
• b5: I5
• b6: I6
• b7: I7
Check the setting and wiring, and reset the power of the whole
system.
If the error is not resolved, there is a possibility that the module is
malfunctioning.
Please contact your local Mitsubishi Electric sales office or
representative.
3601H to
36FFH
No external test pulse of an input terminal Ix corresponding to the bits
which are ON is detected.
36
H
• b0: I0
• b1: I1
• b2: I2
• b3: I3
• b4: I4
• b5: I5
• b6: I6
• b7: I7
Check the wiring between the corresponding input terminal and the
test output.
3701H
T0 unstoppable error
Unable to turn OFF the test output T0.
Check the wiring of I/Os if there is a cross-circuit.
3702H
T1 unstoppable error
Unable to turn OFF the test output T1.
Check the wiring of I/Os if there is a cross-circuit.
3703H
Qx cross-circuit error
A cross-circuit was detected among Q0 to
Q3.
Check the wiring of I/Os if there is a cross-circuit.
3704H
T2 unstoppable error
Unable to turn OFF the test output T2.
Check the wiring of I/Os if there is a cross-circuit.
3705H to
3707H
Short-circuit error
A short-circuit is detected in some outputs.
Check the wiring of I/Os if there is a cross-circuit.
3708H
T3 unstoppable error
Unable to turn OFF the test output T3.
Check the wiring of I/Os if there is a cross-circuit.
3709H to
370FH
Output circuit short-
circuit error
A short-circuit is detected in some outputs.
Check the wiring of I/Os if there is a cross-circuit.
3710H
T0 unstartable error
Unable to turn ON the test output T0.
Check the wiring of I/Os if there is a cross-circuit.
3711H to
371FH
Output circuit short-
circuit error
A short-circuit is detected in some outputs.
Check the wiring of I/Os if there is a cross-circuit.
3720H
T1 unstartable error
Unable to turn ON the test output T1.
Check the wiring of I/Os if there is a cross-circuit.
3721H to
373FH
Output circuit short-
circuit error
A short-circuit is detected in some outputs.
Check the wiring of I/Os if there is a cross-circuit.
3740H
T2 unstartable error
Unable to turn ON the output T2.
Check the wiring of I/Os if there is a cross-circuit.
3741H to
377FH
Output circuit short-
circuit error
A short-circuit is detected in some outputs.
Check the wiring of I/Os if there is a cross-circuit.
3780H
T3 unstartable error
Unable to turn ON the output T3.
Check the wiring of I/Os if there is a cross-circuit.
3781H to
37FFH
Output circuit short-
circuit error
A short-circuit is detected in some outputs.
Check the wiring of I/Os if there is a cross-circuit.
Error code
Error name
Description
Corrective action
Summary of Contents for MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Page 2: ......
Page 29: ...1 OVERVIEW 27 1 MEMO ...
Page 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Page 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Page 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Page 171: ...I 169 MEMO ...
Page 175: ......