140
APPX
Appendix 5 Buffer Memory
Input signals
The status of a safety extension module can be checked in the buffer memory.
■
Buffer memory address
The buffer memory address of this area is as follows.
■
List of input signals
■
Module READY
It turns ON after the completion of the initial processing of the CPU module when the power of the module is turned ON or
reset.
■
Module Safety READY
It turns ON after the completion of the initial processing of the safety extension module when the power of the module is
turned ON or reset.
When the safety control diagnostic information is not updated correctly, Module READY is turned OFF.
■
Error flag
It turns ON when an error occurs in a safety extension module (including a safety expansion module).
Safety control
Number of units connected
The number of connected safety extension modules is stored.
■
Buffer memory address
The buffer memory address of this area is as follows.
Buffer memory name
Address
Input signals
69
Buffer memory
Description
b0
Module READY
b1
Module Safety READY
b2 to 14
Unavailable
b15
Error flag
Buffer memory name
Address
Number of units connected
71
OFF
ON
'Latest error code' (Un\G0)
'Error flag'
(Un\G69, b15)
Error
0
Summary of Contents for MITSUBISHI ELECTRIC MELSEC iQ-F FX5
Page 2: ......
Page 29: ...1 OVERVIEW 27 1 MEMO ...
Page 40: ...38 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 90: ...88 5 SYSTEM CONFIGURATION MEMO ...
Page 112: ...110 7 PARAMETER SETTINGS 7 1 Refresh Setting MEMO ...
Page 117: ...9 COMMISSIONING 9 2 Considerations for Inspection 115 9 MEMO ...
Page 171: ...I 169 MEMO ...
Page 175: ......