Parameter Description
Parameter Description
•
The run direction is set in binary form (8-bit), then translated to decimal form and stored in P.121.
‘1’ denotes run forward, and ‘0’ denotes run reverse. The highest bit is the run direction of section 8,
and the lowest bit is the direction of section 1.
For example: Suppose that section 1 for run forward, section 2 for run reverse, section 3 for run
reverse, section 4 for run forward, section 5 for run reverse, section 6 for run forward,
section 7 for run forward, and section 8 for run reverse, then the value in binary form
is 01101001:
P.121=0×27+1×26+1×25+0×24+1×23+0×22+0×21+1×20=105
•
When P.122=0, it won’t run circularly.
•
When the value of P.122 is 1~8, it is the initialization section of the cycle running.
For example: When P.122=3, the inverter will run circularly from the third section to the eighth
section after it finishes the running from the first section to the eighth section.
When P.123=0, the acceleration time is determined by
P.7
, and the deceleration time is
determined by
P.8
.
When P.123=1, the acceleration time and deceleration time are both determined by
P.111~P.118.
2. Manually operation circle mode
Wiring pattern for manually operation circle mode terminals
•
Connect an impulse type switch between RL and SD.
•
After turning on the power, set
P.80
=35 according to the terminal wiring. At this time, inverter is at
standby.
frequency
R
un
fo
rw
ar
d
R
un
re
ve
rs
e
P.111
P.101
P.112
P.113
P.114
P.115
P.102
pause
P.103
P.104
P.116
P.105
P.106
P.117
P.107
P.118
P.108
P.118
RL
INV
SD