5.37 Frequency Jump (P.91~P.96)
P.91~P.96 “Frequency jump”
To avoid the system mechanical resonance frequency, three sets of jump frequencies are presented:
P.91 and P.92 the first set, P.93 and P.94 the second set, and P.95 and P.96 the third set.
Parameter
Factory Setting
Setting Range
Remarks
91~96
9999
0~650Hz, 9999
9999: invalid
P.91
P.92 P.93 P.94 P.95 P.96
Output
frequency
(Hz)
<Setting>
•
For example: Suppose that P.91 = 45 and P.92 = 50
If the target frequency 45Hz, the steady output frequency = the target frequency.
If 45Hz target frequency 50Hz, the steady output frequency = 45Hz.
If 50Hz target frequency, the steady output frequency = the target frequency.
Note: 1. During acceleration/deceleration, the output frequency of the inverter will still pass through the jump
frequency.
2. If P.91=9999 or P.92=9999, the first set of the frequency jump is invalid.
If P.93=9999 or P.94=9999, the second set of the frequency jump is invalid.
If P.95=9999 or P.96=9999, the third set of the frequency jump is invalid.