
8
Project planning
Configuring the EtherCAT® master for MOVIMOT® with XML file
Manual – EtherCAT
®
Interfaces, Field Distributors
72
INFORMATION
Results
•
Either 4 or 10 process data words can be transmitted in each direction. If, for ex-
ample, PDO
OutputData1
(standard 10 PO) is used, PDO
InputData1
(standard
10 PI) must be used as well.
•
Both input PDO or both output PDO may not be activated at the same time.
List of possible process data objects (PDO) for the MFE72 EtherCAT
®
interface
Index
Size
Name
Mapping
Sync Man-
ager
Sync Unit
1600hex
(5632dec)
8 bytes
OutputData1 (standard 4 PO)
Fixed con-
tent
2
0
1601hex
(5633dec)
20 bytes
OutputData1 (Standard 10 PO)
Fixed con-
tent
2
0
1A00hex
(6656dec)
8 bytes
InputData1 (standard 4 PI)
Fixed con-
tent
3
0
1A01hex
(6657dec)
20 bytes
InputData1 (standard 10 PI)
Fixed con-
tent
3
0
Example: Static PDO for 10 cyclic process data words
PO1
MOVIMOT
®
control word 1
PO2
MOVIMOT
®
speed
PO3
MOVIMOT
®
ramp (only if DIP switch S1/2 = "OFF")
PO4
DO0 - DO1 setpoint
PO5
Module control word
PO6
Reserved
PO7
Reserved
PO8
Reserved
PO9
Reserved
PO10
Reserved
The process output data transported with
OutputData1
is assigned according to this
table. The process output data PO1 - PO3 can be connected with various process
data (control words, setpoints) using the process data parameterization in the
MOVIMOT
®
inverter. For further information, refer to the chapter
"
You can control the switching signals for actuators DO0 – DO1 with process output
data PO4, bit 0 – bit 1. The following table shows the assignment of the module con-
trol word for process output data PO5:
Bit
Assignment
0
Reset encoder input
Encoder value PI7/PI0 is set to "0" when Bit 0 experiences a rising edge.
25809148/EN – 01/2019