6
Electrical installation
Installation instructions for fieldbus interfaces, field distributors
Manual – EtherCAT
®
Interfaces, Field Distributors
39
6.2.7
Line contactor
NOTICE
Damage to the MOVIMOT
®
inverter when using the line contactor for jog mode.
Damage to the MOVIMOT
®
inverter.
•
Do not use the line contactor for jog mode, but only for switching the inverter on
and off.
•
Observe a minimum switch-off time of 2 s for the line contactor.
•
Use only a contactor of utilization category AC3 (EN 60947-4-1) as a line con-
tactor.
6.2.8
Installation above 1000 m amsl
MOVIMOT
®
drives with mains voltages of 200 – 240 V or 380 – 500 V can also be op-
erated at an altitude of 1000 – 4000 m amsl. To do so, you must observe the following
basic conditions.
•
At heights above 1000 m amsl, the nominal continuous power is reduced due to
reduced cooling: I
N
reduction by 1% per 100 m.
•
At altitudes of 2000 – 4000 m amsl you must take limiting measures which reduce
the line side overvoltage from category III to category II for the entire system.
25809148/EN – 01/2019