7
Startup
Startup procedure
Manual – EtherCAT
®
Interfaces, Field Distributors
68
5. Make sure the screw plug of the setpoint potentiometer has a seal and screw it in.
NOTICE
Loss of guaranteed degree of protection if the screw plugs on the f1 set-
point potentiometer and X50 diagnostic interface are not installed or not installed
correctly.
Damage to the MOVIMOT
®
inverter.
•
Make sure the screw plug of the setpoint potentiometer has a seal and screw it
in.
6.
3
4
5
6
7
8
Set minimum frequency f
min
with switch f2.
Function
Setting
Detent setting
0
1
2
3
4
5
6
7
8
9
10
Minimum frequency f
min
[Hz]
2
5
7
10
12
15
20
25
30
35
40
7.
3
4
5
6
7
8
If the ramp time is not specified via the fieldbus (S1/2 DIP switch =
"ON"), set the ramp time at the t1 switch of the MOVIMOT
®
inverter.
The ramp time is based on a setpoint step change of 1500 min
-1
(50 Hz).
Function
Setting
Detent setting
0
1
2
3
4
5
6
7
8
9
10
Ramp time t1 [s]
0.1
0.2
0.3
0.5
0.7
1
2
3
5
7
10
8. Check to see if the required direction of rotation on the MOVIMOT
®
inverter has
been enabled.
Terminal R
Terminal L
Meaning
Activated
Activated
•
Both directions of rotation are enabled.
24V
R
L
Activated
Not activated
•
Only CW rotation is enabled
•
Setpoint input for CCW rotation will stop the
drive.
24V
R
L
Not activated
Activated
•
Only CCW rotation is enabled.
•
Setpoint input for CW rotation will stop the
drive.
24V
R
L
25809148/EN – 01/2019