14
Service
Bus diagnostics with MOVITOOLS MotionStudio
Manual – EtherCAT
®
Interfaces, Field Distributors
115
"ERR"
LED lights
up green
1x
Prerequisite:
•
"RUN" LED flashes green (slave is in PRE-OPERATIONAL status).
•
"RUN" LED lights up green 1× (slave is in SAFE-OPERATIONAL
status).
↓
An unprompted state change has occurred. Repair the configuration
error and start the bus in the master again.
↓
Switch the slave to OPERATIONAL state.
↓
Start the process data communication.
"ERR"
LED
flashes
Prerequisite:
•
"RUN" LED flashes green (slave is in PRE-OPERATIONAL status).
•
"RUN" LED lights up green 1x (slave is in SAFE-OPERATIONAL
status).
↓
Invalid configuration. Repair the configuration error and start the bus in
the master again.
↓
Switch the slave to OPERATIONAL state.
↓
Start the process data communication.
14.2
Bus diagnostics with MOVITOOLS
®
MotionStudio
Bus
diagnostics
with
MOVITOOL
S
MotionStud
io
14.2.1
Fieldbus diagnostics with parameter tree
The MF72A fieldbus interface has a diagnostic interface for startup and diagnostics.
This interface allows for bus diagnostics with the parameter tree in the SEW software
MOVITOOLS
®
MotionStudio.
1. Connect the PC/laptop to the MFE fieldbus interface (see chapter "Connecting
PC").
2. Perform an online scan.
25809148/EN – 01/2019