7
Startup
Startup procedure
Manual – EtherCAT
®
Interfaces, Field Distributors
69
Terminal R
Terminal L
Meaning
not activated
Not activated
•
The device is inhibited or the drive is brought
to a stop.
24V
R
L
9. Set the S1/1 and S1/2 DIP switches on the MFE EtherCAT
®
interface according to
your system's requirements.
1
4
3
2
O
N
S1
res. (OFF)
res. (OFF)
PD CONFIG (OFF)
I/O CONFIG (OFF)
8981582219
DIP
switch
Designation
Meaning
S1/1
I/O CONFIG
Configuration of digital inputs and outputs
OFF:
4 DI + 2 DO (factory setting)
ON:
6 DI
S1/2
PD CONFIG
Configuration of process data transfer between MFE
EtherCAT
®
interface and MOVIMOT
®
OFF:
3 PD => higher-level controller ramp (factory
setting)
ON:
2 PD => ramp configuration on t1 DIP switch
of MOVIMOT
®
inverter
10. Place the MOVIMOT
®
inverter and the MFE housing cover on the field distributor
and screw them on.
11. Switch on the 24 V DC supply voltage for the MFE EtherCAT
®
interface and the
MOVIMOT
®
inverter.
Startup has been completed successfully when the MFE... fieldbus interface
shows the following.
•
The green "RUN" LED lights up.
•
The red "SYS-F" LED is not lit.
12. Configure the MFE EtherCAT
®
interface on the EtherCAT
®
master.
INFORMATION
In conjunction with EtherCAT
®
, no further settings are necessary on the drive.
EtherCAT
®
is configured entirely using software tools. For more information on the
configuration, refer to chapter "EtherCAT
®
configuration".
25809148/EN – 01/2019