SENS.413347.015RE
35
for storage
of floating-
point data
(11573,125)
high byte (B3)
low byte (B4)
0xD4
0x80
LSB
Register address 1003
high byte (B1)
low byte (B2)
MSB
0x46
0x34
8.4.3.4 Map of registers
Map of gas detector holding registers is shown in table 8.7 data float24.
Table 8.7
Address
Description of parameter
Designation
Units of
measuring
Data type
0
Correctness of measured parameters:
0 - values 1-2 incorrect
1 - values 1-2 correct
-
-
int16
13
Concentration
CH
% vol.
fraction
int16
16
Concentration
Cn
% LFL
int16
35
Network address of transducer
AA
-
int16
36
Data transfer rate via RS-485:
1 - 2400; 2 - 4800; 3 - 9600;
4 - 14400; 5 - 19200; 6 - 38400
rS
Kbit/s
int16
37
Data transfer mode via RS-485:
0 - 8N1; 1 - 8N2; 2 - 8O2; 3 - 8E2
rP
-
int16
38
Communication protocol via RS-485:
0 - automatic protocol detection;
1 - Modbus RTU protocol;
2 - SENS protocol;
sP
-
int16
1024
Concentration
CH
% vol.
fraction
float32
1030
Concentration
Cn
% LFL
float32
2016
Current current (entered with calibration
command C10)
I
mA
float32
2034
Status byte
bt
-
float32
2064
Data transfer rate via RS-485:
1 - 2400; 2 - 4800; 3 - 9600;
4 - 14400; 5 - 19200; 6 - 38400
rS
-
float32