SENS.413347.015RE
32
Factory setting of address (parameter
Ad
) - from 01 to 08 in accordance with table of
configuration parameters of gas detector configuration data sheet, if otherwise not stated in
purchase order.
Viewing of address is available for operation modes with "user" and "administrator"
access level.
To change address, "administrator" access level is required.
Change of address is as follows:
- enter configuration menu;
- run command
C231
(enter administrator mode);
- scroll and select menu item
Info
;
- scroll to
Ad
subitem, current value of address is displayed;
- to change, enter
Ad
subitem and type new address of gas detector;
- scroll to
End
item and exit with saving parameters;
- run command
C230
(exit administrator mode).
Value of parameter
Ad
must be recorded in the table of configuration parameters of gas
detector configuration data sheet.
If the address of gas detector is unknown, 0 address may be used to enter configuration
mode. At the same time, all other devices having addresses must be disconnected from SENS
line.
ATTENTION!
USE OF 0 ADDRESS TO ENTER CONFIGURATION MODE IS ONLY
REASONABLE FOR VIEWING OF SINGLE DEVICE PARAMETERS; OTHERWISE
PARAMETERS OF multiple DEVICES MAY BE CHANGED BY MISTAKE.
Viewing of error code (parameter
Er
) and version (ID) of firmware (parameter
Pn
) is
performed similar to viewing address, by selection of corresponding menu subitems.
Possible error codes are shown in table 8.5.
Table 8.5
No.
Error code
Description
1
0000
No errors
2
0001
No data exchange with primary transducer
3
0002
Serial number of primary transducer does not match serial number
stored in gas detector memory during initialization.
4
0004
Value of either LL or rS parameters does not match with values stored
in gas detector memory during initialization.
5
0008
Incorrect data received from primary transducer.
6
0010
Power supply voltage of gas detector is below normal
7
0020
Error of both EEPROM copies
8
0030
Errors 6 and 7 at the same time
9
0040
CRC error of programs memory
10
0050
Errors 9 and 6 at the same time
11
0060
Errors 9 and 7 at the same time
12
0070
Error 6, 7 and 9 at the same time
13
0080
Drift of measurement range zero to negative area
8.4.2.16 Working in emulation mode
"Administrator" access level is required to enter emulation mode.
Emulation mode is a special mode of gas detector operation.
Measuring process is suspended in emulation mode, value of measured concentration is
recorded; at the same time, calculation function for other parameters remains available.