SENS.413347.015RE
85
Cont. of table K.1
#
Function
Message format
38
Reset
configuration
changed flag
Query data
No
Response data
No
Error codes
Code
Description
7
Write-protection enabled
16
Access restricted
40
Enter/exit fixed
current mode
Query data
Byte
Typ
e
Value
Description
0-3
float
-
Fixed current value (mA)
Response data
Byte
Typ
e
Value
Description
0-3
float
-
Actual current value (mA)
Error codes
Code
Description
3
Parameter value is too large
4
Parameter value is too small
7
Write-protection enabled
11
Current loop inactive
16
Access restricted
42
Device reset
Query data
No
Response data
No
Error codes
Code
Description
16
Access restricted
43
Zero setting for
primary
variable
Query data
No
Response data
No
Error codes
Code
Description
1
Unknown error code
7
Write-protection enabled
16
Access restricted
Summary of Contents for SG-A1