SEL-701-1 Monitor
Date Code 20011009
SEL
OGIC®
Control Equations and Monitor Logic
Event Triggering SEL
OGIC
Control Equation
B.32
Event Triggering SEL
OGIC
Control Equation
The event report trigger SEL
OGIC
control equation, ER, triggers standard event
reports for conditions other than trip conditions. When setting ER sees a logical 0 to
logical 1 transition, it generates an event report (if the monitor is not already generating
a report that encompasses the new transition). The factory setting shown in
includes a rising-edge operator [/] in front of each of the alarm elements.
This is used to trigger an event report at alarm inception. Falling-edge operators are
used to generate an event report at frequency element dropout, when the system
frequency has stabilized at or near the nominal frequency.