Date Code 20011009
SEL-701-1 Monitor
Modbus
®
RTU Communications Protocol
Modbus Register Map
C.51
038E
Vca
0 if no voltage
option
0
65535
1
038F
kW
0 if no voltage
option
-32768
32767
1
0390
kVAR
0 if no voltage
option
-32768
32767
1
0391
kVA
0 if no voltage
option
-32768
32767
1
0392
Power Factor
0 if no voltage
option
-100
100
1
• 0.01
0393
Frequency
2000
7000
1
• 0.01
0394
% Thermal
Cap
0
65535
1
• 0.1
0395
% Unbalance
Current
0
1000
1
• 0.1
0396-
039F
Reserved
EVENT RECORDS
03A0
Number of
Event Records
0
14
1
03A1
Event
Selection
1
13
1
03A2
Channel
Selection
1
19
1
03A3
1/4 Cycle
-32768
32767
1
03A4
2/4 Cycle
-32768
32767
1
03A5
3/4 Cycle
-32768
32767
1
03A6
1 Cycle
-32768
32767
1
03A7
1 1/4 Cycle
-32768
32767
1
03A8
1 2/4 Cycle
-32768
32767
1
03A9
1 3/4 Cycle
-32768
32767
1
03AA
2 Cycle
-32768
32767
1
03AB
2 1/4 Cycle
-32768
32767
1
03AC
2 2/4 Cycle
-32768
32767
1
Table C.18
Modbus Register Map (Sheet 34 of 36)
Address
(hex)
Field
Sample
Low
High
Step
Type
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...