SEL-701-1 Monitor
Date Code 20011009
SEL-2020/SEL-2030 Compatibility Features
CASCII Command
D.20
"mS" String of maximum m characters (e.g., 10S for a 10
character string)
"yyyy" is the 4-byte hex ASCII representation of the checksum
A compressed ASCII command may require multiple header and data
configuration lines.
If a compressed ASCII request is made for data that are not available (e.g., the
history buffer is empty or invalid event request), the monitor responds with the
following message:
<STX>"No Data Available","0668"<CR>
<ETX>
SEL-701-1 Monitor Command Response Contents
Display the SEL-701-1 Monitor compressed ASCII configuration message by
typing:
CAS <CR>
The monitor replaces the items in
italics
with the actual monitor data.
The SEL-701-1 Monitor sends:
<STX>
"CAS",6,"yyyy"<CR>
"CST",1,"yyyy"<CR>
"1H","FID","yyyy"<CR>
"1D","45S","yyyy"<CR>
"7H","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC,"yyyy"<CR>
"1D","I","I","I","I","I","I","I","yyyy",<CR>
"22H","IA","IB","IC","IN","VA","VB","VC","N","+5V_PS","-
5V_PS","+15V_PS","+28V_PS","TEMP","RAM","ROM","CR_RAM","EEPROM","BATTERY","RTC","LC_TIME","TC_STAR
T","MONITOR"yyyy"<CR>
"1D","12S","12S","12S","12S","12S","12S","12S","12S","12S","12S","12S","12S","12S","12S","12S","12
S","12S","12S","12S","12S","12S","12S","yyyy"<CR>
"CHI",1,"yyyy"<CR>
"1H","FID","yyyy"<CR>
"1D","45S","yyyy"<CR> where n is defined below
"30H","REC_NUM","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC","TYPE","FREQ","THM
CAP(%)","UB_CURR(%)","IA","IB","IC","IN","IG","3I2","WDG(C)","BRG(C)","AMB(C)","OTH(C)","VAB","VBC
","VCA","kW","kVAR","kVA","PF","LD/LG","yyyy"<CR>
"14D","I","I","I","I","I","I","I","I","25S","F","F","F","F","F","F","F","F","F","10S","10S","10S",
"10S","F","F","F","F","F","F","F","5S","yyyy"<CR>
"CEV",1,"yyyy"<CR>
"1H","FID","yyyy"<CR>
"1D","45S","yyyy"<CR>
"7H","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC,"yyyy"<CR>
"1D","I","I","I","I","I","I","I","yyyy"<CR>
"25H","FREQ","SAM/CYC_A","SAM/CYC_D","NUM_OF_CYC","TYPE","IA","IB","IC","IN","IG","3I2","UB_CURR(%
)","THM
CAP(%)","VAB","VBC","VCA","kW","kVAR","kVA","PF","LEAD/LAG","WINDING(C)","BEARING(C)","AMBIENT(C)"
,"OTHER(C)","yyyy"<CR>
"1D","F","I","I","I","25S","F","F","F","F","F","F","F","F","F","F","F","F","F","F","F","5S","10S",
"10S","10S","10S","yyyy"<CR>
"10H","IA","IB","IC","IG","IN","VAB","VBC","VCA","TRIG ","
Names of elements in the Relay Word
separated by spaces
","yyyy"<CR>
"60D","F","F","F","F","F","F","F","F","2S","24S","yyyy"<CR>
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...