SEL-701-1 Monitor
Date Code 20011009
Commissioning
Selected Functional Tests
6.14
NOTE:
Changing settings requires that you enter the Access
Level 2 password. The factory password is 701.
Step 3.
Set the current source phase angles to apply balanced three-phase
currents. Refer to
for the correct angles, which
depend on the PHROT setting.
Step 4.
Reset the motor thermal element using the front-panel Reset Thermal
Model function.
NOTE:
This function requires that you enter the Access Level 2
password. The factory password is 701.
Set the current sources to apply the test current shown in
then turn on the current sources together. Refer back to
to
determine the expected element operating time. For instance, when
the setting CURVE is equal to 4, the thermal element should trip in
4•10 = 40 seconds when applied three-phase current equals three
times the motor full load current setting, FLA. Use the front-panel
Meter Values\Thermal & RTD Data function to view the estimated
Time to Thermal Trip during each test.
NOTE:
Reset the motor thermal model before each test run or
the element will trip faster than expected.
Table 6.6
Thermal Element Expected Trip Times
Applied Current
(A secondary)
Expected Time to Trip
(s)
Measured Time to Trip
(s)
1.2 • FLA
1.5 • FLA
2.0 • FLA
3.0 • FLA
4.0 • FLA
5.0 • FLA
6.0 • FLA
7.0 • FLA
CURVE • 145.7
CURVE • 51.5
CURVE • 23.3
CURVE • 10.0
CURVE • 5.63
CURVE • 3.60
CURVE • 2.50
CURVE • 1.84
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...