Date Code 20011009
SEL-701-1 Monitor
Modbus
®
RTU Communications Protocol
Reading Event Data Using Modbus
C.17
Reading Event Data Using Modbus
The Modbus Register Map provides a feature that allows you to download
complete event data via Modbus. The SEL-701-1 Monitor stores the latest 13 full-
length event reports in nonvolatile memory.
contains a
complete description of the event data.
Download event summary data by writing an event number to 0371h, then reading
the desired data from addresses 0372h through 0395h.
To download analog event data using Modbus, you need to select both the event
number (write to 03A1h) and the analog channel number (write to 03A2h), then read
the 4-sample per cycle event data from addresses 03A3h through 03DEh.
shows the channel assignments.
Table C.17
Assign Event Report Channel Using Address 03A2h
Set 03A2h Equal To
To Read Data From Channel
1
IA
2
IB
3
IC
4
IG
5
IN
6
VA
7
VB
8
VC
9
Relay Word Rows 1 & 2
10
Relay Word Rows 3 & 4
11
Relay Word Rows 5 & 6
12
Relay Word Rows 7 & 8
13
Relay Word Rows 9 & 10
14
Relay Word Row 11 & 12
15
Relay Word Row 12 & 13
16
Relay Word Row 14 & 15
17
Relay Word Row 16 & 17
18
Relay Word Row 18 & 19
19
Relay Word Row 20 & reserved
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...