Date Code 20011009
701-1 Motor Monitor
Date _______________
Page 4 of 22
Created by ___________
The balance of Thermal Element
Settings are used regardless of setting method.
Thermal Capacity Alarm Pickup
Range:
50%–100%
TCAPU
=
Thermal Capacity Used to Start
Range:
20%–100%
TCSTART
=
Use Learned Starting Thermal Capacity
Range:
Y, N
TCLRNEN
=
Motor Stopped Cooling Time
Range:
180–72000 s
COOLTIME
=
Use Learned Cooling Time
(Hidden when RTDOPT = NONE)
Range:
Y, N
COOLEN
=
Overcurrent (O/C) Elements
(Time-delay settings are hidden when their associated pickup settings = OFF)
Level 1 Phase O/C Pickup
Range:
OFF, 0.25–100.00 A; ITAP = 5 A
OFF, 0.05–20.00 A; ITAP = 1 A
50P1P
=
Level 1 Phase O/C Time Delay
Range:
0.00–400.00 s
50P1D
=
Level 2 Phase O/C Pickup
Range:
OFF, 0.25–100.00 A; ITAP = 5 A
OFF, 0.05–20.00 A; ITAP = 1 A
50P2P
=
Level 2 Phase O/C Time Delay
Range:
0.00–400.00 s
50P2D
=
Level 1 Residual O/C Pickup
Range:
OFF, 0.25–100.00 A; ITAP = 5 A
OFF, 0.05–20.00 A; ITAP = 1 A
50G1P
=
Level 1 Residual O/C Time Delay
Range:
0.00–400.00 s
50G1D
=
Level 2 Residual O/C Pickup
Range:
OFF, 0.25–100.00 A; ITAP = 5 A
OFF, 0.05–20.00 A; ITAP = 1 A
50G2P
=
Level 2 Residual O/C Time Delay
Range:
0.00–400.00 s
50G2D
=
Level 1 Neutral O/C Pickup
Range:
OFF, 0.025–10.000 A; INTAP = 5A
OFF, 0.005–2.000 A; INTAP = 1 A
50N1P
=
Level 1 Neutral O/C Time Delay
Range:
0.00–400.00 s
50N1D
=
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...