Date Code 20011009
701-1 Motor Monitor
Date _______________
Page 13 of 22
Created by ___________
VOLTAGE-BASED PROTECTION
Undervoltage (U/V) Elements
(Hidden if no voltage option or if DELTA_Y = Y)
Level 1 Phase-Phase U/V Pickup
Range:
OFF, 1–300 V
27P1P
=
Level 2 Phase-Phase U/V Pickup
Range:
OFF, 1–300 V
27P2P
=
Overvoltage (O/V) Elements
(Hidden if no voltage option or if DELTA_Y = Y)
Level 1 Phase-Phase O/V Pickup
Range:
OFF, 1–300 V
59P1P
=
Level 2 Phase-Phase O/V Pickup
Range:
OFF, 1–300 V
59P2P
=
Undervoltage (U/V) Elements
(Hidden if no voltage option or if DELTA_Y = D)
Level 1 Phase U/V Pickup
Range:
OFF, 1–300 V
27P1P
=
Level 2 Phase U/V Pickup
Range:
OFF, 1–300 V
27P2P
=
Overvoltage (O/V) Elements
(Hidden if no voltage option or if DELTA_Y = D)
Level 1 Phase O/V Pickup
Range:
OFF, 1–300 V
59P1P
=
Level 2 Phase O/V Pickup
Range:
OFF, 1–300 V
59P2P
=
Residual O/V Pickup
(Hidden if SINGLEV = Y)
Range:
OFF, 1–300 V
59GP
=
Reactive Power (VAR) Element Settings
(Hidden if no voltage option)
Negative VAR Alarm Pickup
Range:
OFF, 30–2000 VAR; ITAP = 5 A
OFF, 6–400 VAR; ITAP = 1 A
NVARAP
=
Positive VAR Alarm Pickup
(Hidden if NVARAP = OFF)
Range:
30–2000 VAR; ITAP = 5 A
6–400 VAR; ITAP = 1 A
PVARAP
=
VAR Alarm Time Delay
(Hidden if NVARAP = OFF)
Range:
0.00–400.00 s
VARAD
=
Negative VAR Trip Pickup
Range:
OFF, 30–2000 VAR; ITAP = 5 A
OFF, 6–400 VAR; ITAP = 1 A
NVARTP
=
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...