Date Code 20011009
SEL-701-1 Monitor
Installation
Monitor Connections
2.19
shows typical maximum RTD lead lengths for various wire gauges. Use
shielded cable for the RTD connections, with the shield connected to ground at the
monitor. Two shield connection terminals, A01 and A30, are provided for grounding at
the monitor. You may also connect shield wires to the common connection terminals,
A04, A09, A14, A19, A24, and A29.
Table 2.1
Typical Maximum RTD Lead Length
RTD Lead AWG
Platinum or Nickel RTD
Copper RTD
24
950 ft
(290 m)
110 ft
(290 m)
22
1500 ft
(455 m)
180 ft
(54 m)
20
2400 ft
(730 m)
290 ft
(88 m)
18
3800 ft
(1155 m)
450 ft
(137 m)