Date Code 20011009
701-1 Motor Monitor
Date _______________
Page 5 of 22
Created by ___________
Level 2 Neutral O/C Pickup
Range:
OFF, 0.025–10.000 A; INTAP = 5 A
OFF, 0.005–2.000 A; INTAP = 1 A
50N2P
=
Level 2 Neutral O/C Time Delay
Range:
0.00–400.00 s
50N2D
=
Negative-Sequence O/C Pickup
Range:
OFF, 0.25–100.00 A; ITAP = 5 A
OFF, 0.05–20.00 A; ITAP = 1 A
50QP
=
Negative-Sequence O/C Time Delay
Range:
0.10–400.00 s
50QD
=
Jogging Block Element Settings
Maximum Number of Starts per Hour
Range:
OFF, 1–15
MAXSTART
=
Minimum Time Between Starts
Range:
OFF, 1–150 min
TBSDLY
=
Load-Jam Function Settings
Load-Jam Trip Pickup
Range:
OFF, 0.5–6.0 pu FLA
LJTPU
=
Load-Jam Trip Delay
Range:
0.00–400.0 s
LJTDLY
=
Load-Loss Element Settings
(Hidden when voltage option available)
Load-Loss Alarm Threshold
Range:
OFF, 30–2000 W; ITAP = 5 A
OFF, 6–400 W; ITAP = 1 A
LLAPU
=
(Hidden when LLAPU = OFF)
Load-Loss Trip Threshold
Range:
30–2000 W; ITAP = 5 A
6–400 W; ITAP = 1 A
LLTPU
=
Load-Loss Starting Time Delay
Range:
0–15000 s
LLSDLY
=
Load-Loss Alarm Time Delay
Range:
0.00–400.00 s
LLADLY
=
Load-Loss Trip Time Delay
Range:
0.00–400.00 s
LLTDLY
=
(Hidden when voltage option unavailable)
Load-Loss Alarm Threshold
Range:
OFF, 0.10–1.00 pu FLA
LLAPU
=
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...