Date Code 20011009
SEL-701-1 Monitor
SEL
OGIC®
Control Equations and Monitor Logic
Relay Word Bits
B.11
18
RTD9A3
RTDx Alarm # 3 (x = 1 to 12). Assert when the RTD
temperature exceeds RTDx Alarm #3 setpoint. Deassert
when the RTD temperature is below RTDx Alarm #3
setpoint.
RTD10A3
RTD11A3
RTD12A3
*
Reserved for future use.
*
*
*
19
RTD1T
RTDx Alarm # 1 (x = 1 to 12). Assert when the RTD
temperature exceeds RTDx Alarm #1 setpoint. Deassert
when the RTD temperature is below RTDx Alarm #1
setpoint.
RTD2T
RTD3T
RTD4T
RTD5T
RTD6T
RTD7T
RTD8T
20
RTD9T
RTDx Trip (x = 1 to 12). Assert when the RTD temperature
exceeds RTDx Trip setpoint. Deassert when the RTD
temperature is below RTDx Trip setpoint.
RTD10T
RTD11T
RTD12T
*
Reserved for future use.
*
*
*
Table B.2
Relay Word Bit Definitions for SEL-701-1
(Sheet 7 of 7)
Row Bit
Definition