Date Code 20011009
SEL-701-1 Monitor
SEL
OGIC®
Control Equations and Monitor Logic
Remote Control Switches
B.35
Remote Bit Application Ideas
With SEL
OGIC
control equations, you can use the remote bits to trip or start the
motor or to open, close, or pulse monitor output contacts for other purposes.
Also, you can use remote bits like a contact input in operating latch control
switches. Pulse (momentarily operate) the remote bits for this application.
Remote Bit States Are Not Retained When Power Is Lost
The states of the remote bits (Relay Word bits RB1–RB4) are not retained if
power to the monitor is lost and then restored. The remote control switches always
come back in the OFF position (corresponding remote bit is deasserted to logical 0)
when power is restored to the monitor.